1 Wrong phase fault
|
Phenomenon |
Trouble shooting |
|
LED L17 on the rectifying board of DC power unit is on |
Check if the sequency of the three phase input power is right. |
2 Over current fault
|
Phenomenon |
Trouble shooting |
|
LED L18 or L16 on the rectifying board of DC power unit is on. |
1. Check if the rectifying SCR is damaged (refer to 9.3.4). 2. Check if the flat wave reactor burned. 3. Check if the inverter unit power components are broken. 4. Check if the resistance of the inductor is loose. |
Note: Any of the above fault can led to stop protection and show "welder failure" on the touch screen.
3 Full load when start welder
|
Phenomenon |
Trouble shooting |
|
Rectifying board in the DC power unit indicates normally. |
Check if the power adjust potentiometer is broken. 2. Check the rectifying board is broken. |